Telemetry Payload

Status: Acitve | Applies to: all SPM / SDM Open Wi-Fi branches | Updated: 2026-10-17

The device periodically builds one telemetry JSON (a "packet"). The same JSON is sent unchanged over several channels, so its fields are maintained only on this page.

1. Which channels carry it

Channel
How to get it
Period

MQTT

Subscribe to {Model}/{SN}/data

Default 5 s, configurable (MQTT period, minimum 1 s)

HTTP / HTTPS

GET /data; the data field of GET /snapshot

On demand, latest packet on every call

WebSocket

Pushed automatically after you connect

Default 5000 ms, 100 ms to 86400000 ms

UDP

Sent to the configured target IP:port

Default 5000 ms, minimum 100 ms

Modbus TCP

Register reads, not JSON; see Modbus TCP

On demand

BLE

cmd=read, then read the characteristic

On demand

The periods are independent; how to change them is in the Business Command Reference (mqtt, udp, setInterval). The value on the device wins over any factory default and can be read from the model response (MQTT period MI, UDP period UI; in HTTP /model they are mqttInterval, udpInterval, wsInterval).

2. Common fields

Present on every model:

Field
Type
Description

Post

number

Packet counter, +1 for each packet built, back to 0 after a reboot. Use it to spot loss and duplicates

Time

number

Unix timestamp (seconds). The device syncs by NTP; do not trust it before the first sync

IP

string

Device IPv4

Rssi

number

Wi-Fi signal strength in dBm, negative

FWVersion

string

Wi-Fi module firmware version, for example "5.1.16"

MCUVersion

string

Metering MCU firmware version, for example "003.00.13"

SerialNumber

string

Device serial number, 12 uppercase hex characters (Wi-Fi MAC)

ProductModel

string

Model, for example SPM01, SPM02, SDM01_3PN

TP

number

Model code, see Section 3

3. TP model code

TP is a model code, not a phase count.

TP
Model
Phases
Seen on

1

SPM01

single

Basic, Lite

2

SDM01_1PN

single

Basic, Lite

3

SPM02

three

Basic, Lite

4

SDM01_3PN

three

Basic, Lite

5

SDM02

split

Basic, Lite

8

all SDM01 Gen2 models

single or three

Basic+, Pro

9

other models

—

not covered here

Points to remember:

  • On SDM01 Gen2 (Basic+ / Pro) TP is always 8, so it cannot tell single phase from three phase.

  • Decide by ProductModel or by which fields exist (VoltageX means three-phase, VoltageL1 means split-phase, Voltage means single-phase). Do not hard-code TP.

  • An earlier published page said "TP 1 = single phase, 3 = three phase"; that is only true for SPM01 / SPM02.

4. Fields per model

Values are strings with fixed decimals: voltage 1, current and power 3, power factor and frequency 2, energy 2, unbalance 0. Units: V, A, kW, kVA, kVAR, Hz, kWh, %.

4.1 Single-phase (SPM01, SDM01_1PN)

Field
Unit
Description

Voltage

V

Voltage

Current

A

Current

ActivePower

kW

Active power

ApparentPower

kVA

Apparent power

PowerFactor

—

Power factor

Frequency

Hz

Frequency

ForwardEnergy

kWh

Forward (import) active energy

ReverseEnergy

kWh

Reverse (export) active energy

TotalEnergy

kWh

Forward + reverse

4.2 Split-phase (SDM02)

Field
Unit

VoltageL1, VoltageL2

V

CurrentL1, CurrentL2, TotalCurrent

A

ActivePowerL1, ActivePowerL2, TotalActivePower

kW

ReactivePowerL1, ReactivePowerL2, TotalReactivePower

kVAR

ApparentPowerL1, ApparentPowerL2, TotalApparentPower

kVA

PowerFactorL1, PowerFactorL2, OverallPowerFactor

—

AverageVoltageL_N

V

AverageLineCurrent

A

Frequency

Hz

ForwardEnergyL1, ForwardEnergyL2, TotalForwardEnergy

kWh

ReverseEnergyL1, ReverseEnergyL2, TotalReverseEnergy

kWh

TotalEnergyL1, TotalEnergyL2, TotalEnergy

kWh

4.3 Three-phase (SPM02, SDM01_3PN)

X, Y, Z are phases A, B, C.

Field
Unit

VoltageX, VoltageY, VoltageZ

V

CurrentX, CurrentY, CurrentZ, TotalCurrent

A

ActivePowerX, ActivePowerY, ActivePowerZ, TotalActivePower

kW

ReactivePowerX, ReactivePowerY, ReactivePowerZ, TotalReactivePower

kVAR

ApparentPowerX, ApparentPowerY, ApparentPowerZ, TotalApparentPower

kVA

PowerFactorX, PowerFactorY, PowerFactorZ, OverallPowerFactor

—

AverageVoltageL_N

V

AverageLineCurrent

A

UnbalanceLineCurrents

%

Frequency

Hz

ForwardEnergyX, ForwardEnergyY, ForwardEnergyZ, TotalForwardEnergy

kWh

ReverseEnergyX, ReverseEnergyY, ReverseEnergyZ, TotalReverseEnergy

kWh

TotalEnergyX, TotalEnergyY, TotalEnergyZ, TotalEnergy

kWh

Field sets differ slightly between firmware versions (for example TotalCurrent, TotalReactivePower, TotalApparentPower, AverageVoltageL_N, AverageLineCurrent and TotalEnergy* exist on 5.1.16 and may be missing on older versions). Use a field if it is there and ignore it if it is not.

5. Examples

Single-phase:

Three-phase:

6. Generic format (commonmode)

{"cmd":"commonmode","value":1} switches the report format from the default "BT format" (the sections above) to a "generic format" that follows the common smart-meter NotifyStatus message shape; value=0 switches back. The setting is saved and survives reboots.

What changes in the generic format:

  • Common fields use lowercase keys: tp, src (full device name), dst (always "*"), method (always "NotifyStatus"), ip, rssi, fwversion, serialnumber, mcuversion, post.

  • Measurements sit under params: the timestamp is params.ts, the values are in params["em:0"], and they are numbers, not strings.

  • Power is in W and energy in Wh (the BT format uses kW and kWh; the device multiplies by 1000).

  • Single-phase keys: act_power, aprt_power, current, freq, pf, voltage, act_energy, act_ret_energy.

  • Three-phase keys: prefix a_ / b_ / c_ with act_power, aprt_power, current, freq, pf, voltage; plus total_act_power, total_aprt_power, total_current, a_total_act_energy, a_total_act_ret_energy (same for B and C), total_act, total_act_ret. When a phase voltage is 50 V or lower, that phase's *_freq is 0.

  • params["emdata:0"] is always an empty object; read energy from the keys in em:0.

With the generic format on, the Modbus TCP register layout also changes to that style. This documentation does not cover that layout; keep commonmode=0 if you need the standard register map.

7. Parsing advice

  1. Look at ProductModel and the field names to choose single-phase, split-phase or three-phase parsing; do not rely on TP.

  2. Parse numeric strings as decimal floats and do not assume the number of decimals stays fixed.

  3. Use Post to detect duplicates and loss; after a reboot Post returns to a small value, so do not treat a decrease as an error.

  4. Before using Time, check that it is not obviously small (not yet synced).

  5. Ignore unknown fields and do not treat missing fields as errors.

Last updated