Telemetry Payload
The device periodically builds one telemetry JSON (a "packet"). The same JSON is sent unchanged over several channels, so its fields are maintained only on this page.
1. Which channels carry it
MQTT
Subscribe to {Model}/{SN}/data
Default 5 s, configurable (MQTT period, minimum 1 s)
HTTP / HTTPS
GET /data; the data field of GET /snapshot
On demand, latest packet on every call
WebSocket
Pushed automatically after you connect
Default 5000 ms, 100 ms to 86400000 ms
UDP
Sent to the configured target IP:port
Default 5000 ms, minimum 100 ms
Modbus TCP
Register reads, not JSON; see Modbus TCP
On demand
BLE
cmd=read, then read the characteristic
On demand
The periods are independent; how to change them is in the Business Command Reference (mqtt, udp, setInterval). The value on the device wins over any factory default and can be read from the model response (MQTT period MI, UDP period UI; in HTTP /model they are mqttInterval, udpInterval, wsInterval).
2. Common fields
Present on every model:
Post
number
Packet counter, +1 for each packet built, back to 0 after a reboot. Use it to spot loss and duplicates
Time
number
Unix timestamp (seconds). The device syncs by NTP; do not trust it before the first sync
IP
string
Device IPv4
Rssi
number
Wi-Fi signal strength in dBm, negative
FWVersion
string
Wi-Fi module firmware version, for example "5.1.16"
MCUVersion
string
Metering MCU firmware version, for example "003.00.13"
SerialNumber
string
Device serial number, 12 uppercase hex characters (Wi-Fi MAC)
ProductModel
string
Model, for example SPM01, SPM02, SDM01_3PN
TP
number
Model code, see Section 3
3. TP model code
TP is a model code, not a phase count.
1
SPM01
single
Basic, Lite
2
SDM01_1PN
single
Basic, Lite
3
SPM02
three
Basic, Lite
4
SDM01_3PN
three
Basic, Lite
5
SDM02
split
Basic, Lite
8
all SDM01 Gen2 models
single or three
Basic+, Pro
9
other models
—
not covered here
Points to remember:
On SDM01 Gen2 (Basic+ / Pro)
TPis always8, so it cannot tell single phase from three phase.Decide by
ProductModelor by which fields exist (VoltageXmeans three-phase,VoltageL1means split-phase,Voltagemeans single-phase). Do not hard-codeTP.An earlier published page said "
TP1 = single phase, 3 = three phase"; that is only true for SPM01 / SPM02.
4. Fields per model
Values are strings with fixed decimals: voltage 1, current and power 3, power factor and frequency 2, energy 2, unbalance 0. Units: V, A, kW, kVA, kVAR, Hz, kWh, %.
4.1 Single-phase (SPM01, SDM01_1PN)
Voltage
V
Voltage
Current
A
Current
ActivePower
kW
Active power
ApparentPower
kVA
Apparent power
PowerFactor
—
Power factor
Frequency
Hz
Frequency
ForwardEnergy
kWh
Forward (import) active energy
ReverseEnergy
kWh
Reverse (export) active energy
TotalEnergy
kWh
Forward + reverse
4.2 Split-phase (SDM02)
VoltageL1, VoltageL2
V
CurrentL1, CurrentL2, TotalCurrent
A
ActivePowerL1, ActivePowerL2, TotalActivePower
kW
ReactivePowerL1, ReactivePowerL2, TotalReactivePower
kVAR
ApparentPowerL1, ApparentPowerL2, TotalApparentPower
kVA
PowerFactorL1, PowerFactorL2, OverallPowerFactor
—
AverageVoltageL_N
V
AverageLineCurrent
A
Frequency
Hz
ForwardEnergyL1, ForwardEnergyL2, TotalForwardEnergy
kWh
ReverseEnergyL1, ReverseEnergyL2, TotalReverseEnergy
kWh
TotalEnergyL1, TotalEnergyL2, TotalEnergy
kWh
4.3 Three-phase (SPM02, SDM01_3PN)
X, Y, Z are phases A, B, C.
VoltageX, VoltageY, VoltageZ
V
CurrentX, CurrentY, CurrentZ, TotalCurrent
A
ActivePowerX, ActivePowerY, ActivePowerZ, TotalActivePower
kW
ReactivePowerX, ReactivePowerY, ReactivePowerZ, TotalReactivePower
kVAR
ApparentPowerX, ApparentPowerY, ApparentPowerZ, TotalApparentPower
kVA
PowerFactorX, PowerFactorY, PowerFactorZ, OverallPowerFactor
—
AverageVoltageL_N
V
AverageLineCurrent
A
UnbalanceLineCurrents
%
Frequency
Hz
ForwardEnergyX, ForwardEnergyY, ForwardEnergyZ, TotalForwardEnergy
kWh
ReverseEnergyX, ReverseEnergyY, ReverseEnergyZ, TotalReverseEnergy
kWh
TotalEnergyX, TotalEnergyY, TotalEnergyZ, TotalEnergy
kWh
Field sets differ slightly between firmware versions (for example TotalCurrent, TotalReactivePower, TotalApparentPower, AverageVoltageL_N, AverageLineCurrent and TotalEnergy* exist on 5.1.16 and may be missing on older versions). Use a field if it is there and ignore it if it is not.
5. Examples
Single-phase:
Three-phase:
6. Generic format (commonmode)
{"cmd":"commonmode","value":1} switches the report format from the default "BT format" (the sections above) to a "generic format" that follows the common smart-meter NotifyStatus message shape; value=0 switches back. The setting is saved and survives reboots.
What changes in the generic format:
Common fields use lowercase keys:
tp,src(full device name),dst(always"*"),method(always"NotifyStatus"),ip,rssi,fwversion,serialnumber,mcuversion,post.Measurements sit under
params: the timestamp isparams.ts, the values are inparams["em:0"], and they are numbers, not strings.Power is in W and energy in Wh (the BT format uses kW and kWh; the device multiplies by 1000).
Single-phase keys:
act_power,aprt_power,current,freq,pf,voltage,act_energy,act_ret_energy.Three-phase keys: prefix
a_/b_/c_withact_power,aprt_power,current,freq,pf,voltage; plustotal_act_power,total_aprt_power,total_current,a_total_act_energy,a_total_act_ret_energy(same for B and C),total_act,total_act_ret. When a phase voltage is 50 V or lower, that phase's*_freqis 0.params["emdata:0"]is always an empty object; read energy from the keys inem:0.
With the generic format on, the Modbus TCP register layout also changes to that style. This documentation does not cover that layout; keep commonmode=0 if you need the standard register map.
7. Parsing advice
Look at
ProductModeland the field names to choose single-phase, split-phase or three-phase parsing; do not rely onTP.Parse numeric strings as decimal floats and do not assume the number of decimals stays fixed.
Use
Postto detect duplicates and loss; after a rebootPostreturns to a small value, so do not treat a decrease as an error.Before using
Time, check that it is not obviously small (not yet synced).Ignore unknown fields and do not treat missing fields as errors.