Modbus TCP Map

Status: Draft| Applies to: all SPM / SDM Open Wi-Fi branches (Modbus TCP over TLS only on Basic+ and Pro) | Updated: 2026-10-17

🔍 Feature: Device Locating via LED When multiple meters are installed in a dense electrical panel, send 0x5055 to a specific device's Slave ID. The target meter's LED will blink rapidly for 15 seconds, allowing field engineers to visually identify the physical device corresponding to that IP/Slave ID.

Modbus TCP is the most common way for PLCs, industrial gateways and EMS to read the meter. The device is a Modbus TCP server (slave) on port 502: you poll it and read the electrical values from fixed registers. It does not push anything by itself.

1. Introduction

Item
Description

Port

502

Unit ID (Slave ID)

The firmware does not check the Unit ID and echoes it back; use 1

Function codes

0x03 read holding registers, 0x04 read input registers (same data), 0x06 write single register (control registers only)

Readable window

Registers 978 ~ 1077 (100 registers), see Section 4

Word order

A 32-bit value uses two registers, high word at the lower address (ABCD, big-endian)

Switch

Function bit 15 (enablemodbustcp, see Business Command Reference); the server runs only when the bit is set

Concurrent connections

Basic / Lite: 2, Basic+: 1, Pro: 2 (the same number as the TLS slots, see Overview)

Frame size

At most 600 bytes per receive

Which map to use (single / split / three phase) is decided by the product model; read the model string from register 984 (for example SDM01_3PN) or from the model command.

Type
Products (ordering numbers)

Single-phase

SPM01-D2EW, SPM01-D1EW, SPM01-U1EW

Split-phase

SDM02-EW-12, SDM02-EW-20, SDM02-EW-10U

Three-phase

SPM02-D2EW, SPM02-D1EW, SPM02-U1EW, SDM01-EWM-12, SDM01-EWM-20

2. Connecting

2.1 Plain connection

Open a TCP connection to <device IP>:502 and send standard Modbus TCP frames (MBAP header + PDU). Find the IP with mDNS discovery or from the router.

Connection behavior of the firmware:

  • A connection may stay open and be reused. If it is idle for 30 seconds the device closes it (custom builds may use 12 s). A client that polls more slowly than that must reconnect.

  • When all slots are in use, a new connection is not accepted until one slot is released.

  • The device answers one request at a time. If several complete frames are already queued in the receive buffer, only the newest one is answered. Always wait for the response before sending the next request.

  • A frame whose declared length does not match is dropped without a response; the client sees a timeout.

  • Recommended minimum interval between two requests: 150 ms. Polling faster than about once per second is normally unnecessary for energy data.

The Gitbook page says the device accepts only one connection and resets the socket after every read, and asks you to reconnect for every request. The meter keeps the connection. Reconnecting for every request still works and is the safest choice for simple clients, so the recommendation stays compatible. See the CHANGELOG entry for this discrepancy.

2.2 Modbus TCP over TLS

On Basic+ and Pro you can enable Modbus TLS (function bit 14 plus bit 15 in enabletls / enablemodbustcp); the TLS server then also listens on 502. TLS slots are shared with MQTTS, HTTPS and WSS; the service priority is MQTTS > HTTPS > WSS > Modbus TLS, and a Modbus service without a slot falls back to plaintext. Details and limits are in the Overview. Many PLCs and gateways cannot do Modbus over TLS; in that case keep the plaintext connection on a trusted network segment.

3. Function codes and exceptions

Function code
Behavior

0x03 / 0x04

Read registers inside the 978 ~ 1077 window. Start address plus quantity must stay inside the window

0x06

Only the two control registers in Section 5 are writable

Any other

Exception 01

Exception responses:

Exception code
When

01 Illegal function

Function code other than 03 / 04 / 06 (including 0x10 write multiple registers)

02 Illegal data address

Read range outside 978 ~ 1077, or write address that is not a control register

03 Illegal data value

Control register written with a value other than the magic value

05

Frame shorter than 12 bytes (non-standard use of this code)

4. Register map

The map below is for the default report mode commonmode = 0. When the device is switched to the generic format (commonmode = 1, see the Business Command Reference), the Modbus read map is switched to a different layout and the tables below do not apply. The device also has mda / minvert commands that remap register addresses or swap bytes for custom integrations. They are not covered here. mda also sets commonmode back to 0 and turns Modbus TCP on. The factory layout is the one below.

4.1 Product identification (base address 978)

Identical on all models. Strings are ASCII packed two characters per register, first character in the high byte. Unused characters are 0.

Address (DEC)
Address (HEX)
Description
Registers
Type
Example

978

0x03D2

MAC address

6

String (12 characters)

45705E597760

984

0x03D8

Product model

5

String (10 characters)

SDM01_3PN

989

0x03DD

MCU firmware version

5

String (10 characters)

003.00.13

994

0x03E2

Wi-Fi signal strength

1

UINT16

68 means -68 dBm

995

0x03E3

System time

2

UINT32, high word first

Unix seconds

997

0x03E5

Wi-Fi firmware version

3

String (6 characters)

5.1.16

Register 994 holds the absolute value of the RSSI (the firmware writes -rssi into an unsigned register). The Gitbook page describes it as a negative dBm value; in the data you read a positive number. Register 989 is the MCU firmware, register 997 the Wi-Fi firmware (the two examples on the Gitbook page are swapped).

4.2 Single-phase metering data

Address (DEC)
Address (HEX)
Description
Type
Range
Unit

1000

0x03E8

Voltage

FLOAT32

0 ~ 1000

V

1002

0x03EA

Current

FLOAT32

0 ~ 1000

A

1004

0x03EC

Active power

FLOAT32

-1000 ~ 1000

kW

1006

0x03EE

Power factor

FLOAT32

-1.0 ~ 1.0

—

1008

0x03F0

Frequency

FLOAT32

0 ~ 1000

Hz

1010

0x03F2

Import active energy

FLOAT32

±1999999999

kWh

1012

0x03F4

Export active energy

FLOAT32

±1999999999

kWh

1014

0x03F6

Total active energy (import + export)

FLOAT32

±1999999999

kWh

4.3 Split-phase metering data

Address (DEC)
Address (HEX)
Description
Type
Range
Unit

1000

0x03E8

Voltage L1-N

FLOAT32

0 ~ 1000

V

1002

0x03EA

Voltage L2-N

FLOAT32

0 ~ 1000

V

1006

0x03EE

Current L1

FLOAT32

0 ~ 1000

A

1008

0x03F0

Current L2

FLOAT32

0 ~ 1000

A

1012

0x03F4

Active power L1

FLOAT32

-1000 ~ 1000

kW

1014

0x03F6

Active power L2

FLOAT32

-1000 ~ 1000

kW

1018

0x03FA

Reactive power L1

FLOAT32

-1000 ~ 1000

kVAR

1020

0x03FC

Reactive power L2

FLOAT32

-1000 ~ 1000

kVAR

1024

0x0400

Apparent power L1

FLOAT32

-1000 ~ 1000

kVA

1026

0x0402

Apparent power L2

FLOAT32

-1000 ~ 1000

kVA

1030

0x0406

Power factor L1

FLOAT32

-1.0 ~ 1.0

—

1032

0x0408

Power factor L2

FLOAT32

-1.0 ~ 1.0

—

1036

0x040C

Average voltage L-N

FLOAT32

0 ~ 1000

V

1038

0x040E

Average line current

FLOAT32

0 ~ 1000

A

1040

0x0410

Unbalanced line currents

FLOAT32

-300 ~ 300

%

1042

0x0412

Total line currents

FLOAT32

0 ~ 3000

A

1044

0x0414

Total active power

FLOAT32

-3000 ~ 3000

kW

1046

0x0416

Total reactive power

FLOAT32

-3000 ~ 3000

kVAR

1048

0x0418

Total apparent power

FLOAT32

-3000 ~ 3000

kVA

1050

0x041A

Total power factor

FLOAT32

-1.0 ~ 1.0

—

1052

0x041C

Frequency

FLOAT32

0 ~ 1000

Hz

1054

0x041E

Total import active energy

FLOAT32

±1999999999

kWh

1056

0x0420

Total export active energy

FLOAT32

±1999999999

kWh

1058

0x0422

Total import & export active energy

FLOAT32

±1999999999

kWh

1060

0x0424

L1 import active energy

FLOAT32

±1999999999

kWh

1062

0x0426

L1 export active energy

FLOAT32

±1999999999

kWh

1064

0x0428

L1 import & export active energy

FLOAT32

±1999999999

kWh

1066

0x042A

L2 import active energy

FLOAT32

±1999999999

kWh

1068

0x042C

L2 export active energy

FLOAT32

±1999999999

kWh

1070

0x042E

L2 import & export active energy

FLOAT32

±1999999999

kWh

4.4 Three-phase metering data

Address (DEC)
Address (HEX)
Description
Type
Range
Unit

1000

0x03E8

Voltage A-N

FLOAT32

0 ~ 1000

V

1002

0x03EA

Voltage B-N

FLOAT32

0 ~ 1000

V

1004

0x03EC

Voltage C-N

FLOAT32

0 ~ 1000

V

1006

0x03EE

Current A

FLOAT32

0 ~ 1000

A

1008

0x03F0

Current B

FLOAT32

0 ~ 1000

A

1010

0x03F2

Current C

FLOAT32

0 ~ 1000

A

1012

0x03F4

Active power A

FLOAT32

-1000 ~ 1000

kW

1014

0x03F6

Active power B

FLOAT32

-1000 ~ 1000

kW

1016

0x03F8

Active power C

FLOAT32

-1000 ~ 1000

kW

1018

0x03FA

Reactive power A

FLOAT32

-1000 ~ 1000

kVAR

1020

0x03FC

Reactive power B

FLOAT32

-1000 ~ 1000

kVAR

1022

0x03FE

Reactive power C

FLOAT32

-1000 ~ 1000

kVAR

1024

0x0400

Apparent power A

FLOAT32

-1000 ~ 1000

kVA

1026

0x0402

Apparent power B

FLOAT32

-1000 ~ 1000

kVA

1028

0x0404

Apparent power C

FLOAT32

-1000 ~ 1000

kVA

1030

0x0406

Power factor A

FLOAT32

-1.0 ~ 1.0

—

1032

0x0408

Power factor B

FLOAT32

-1.0 ~ 1.0

—

1034

0x040A

Power factor C

FLOAT32

-1.0 ~ 1.0

—

1036

0x040C

Average voltage L-N

FLOAT32

0 ~ 1000

V

1038

0x040E

Average line current

FLOAT32

0 ~ 1000

A

1040

0x0410

Unbalanced line currents

FLOAT32

-300 ~ 300

%

1042

0x0412

Total line currents

FLOAT32

0 ~ 3000

A

1044

0x0414

Total active power

FLOAT32

-3000 ~ 3000

kW

1046

0x0416

Total reactive power

FLOAT32

-3000 ~ 3000

kVAR

1048

0x0418

Total apparent power

FLOAT32

-3000 ~ 3000

kVA

1050

0x041A

Total power factor

FLOAT32

-1.0 ~ 1.0

—

1052

0x041C

Frequency

FLOAT32

0 ~ 1000

Hz

1054

0x041E

Total import active energy

FLOAT32

±1999999999

kWh

1056

0x0420

Total export active energy

FLOAT32

±1999999999

kWh

1058

0x0422

Total import & export active energy

FLOAT32

±1999999999

kWh

1060

0x0424

Phase A import active energy

FLOAT32

±1999999999

kWh

1062

0x0426

Phase A export active energy

FLOAT32

±1999999999

kWh

1064

0x0428

Phase A import & export active energy

FLOAT32

±1999999999

kWh

1066

0x042A

Phase B import active energy

FLOAT32

±1999999999

kWh

1068

0x042C

Phase B export active energy

FLOAT32

±1999999999

kWh

1070

0x042E

Phase B import & export active energy

FLOAT32

±1999999999

kWh

1072

0x0430

Phase C import active energy

FLOAT32

±1999999999

kWh

1074

0x0432

Phase C export active energy

FLOAT32

±1999999999

kWh

1076

0x0434

Phase C import & export active energy

FLOAT32

±1999999999

kWh

4.5 Reading FLOAT32 values

All measurements are FLOAT32, two registers each, high word first. For example the registers 0x435C 0x0000 are 0x435C0000 = 220.0. In most libraries this is "Big Endian, word order big / ABCD". If the numbers look wrong (for example 1.6e-41 or huge values) your tool is using word-swapped order (CDAB): switch the setting.

  • Units: power in kW / kVAR / kVA, energy in kWh, voltage V, current A. This is the same unit as the telemetry JSON in Telemetry Payload; the firmware copies the meter chip registers, so values are not rescaled.

  • Addresses that are not listed in a table (for example 1004 on the split-phase map) are inside the window but have no defined meaning; do not use them.

5. Control registers

Write with function code 0x06. These registers are outside the read window and cannot be read.

Address (DEC)
Address (HEX)
Function
Value to write

10001

0x2711

Reset energy accumulators

0x51AA (20906)

10002

0x2712

Locate: blink the LED

0x5055 (20565)

  • A wrong value returns exception 03; a wrong address returns 02.

  • Locate blinks the LED (about 15 seconds according to the Gitbook page) so you can find the physical meter in a crowded panel; it does the same as the location command.

  • Reset energy is irreversible. It is the same as the zero command.

The published page lists the locate register at 10000 (0x2710). Over Modbus TCP the Wi-Fi module does not handle 10000: locate is at 10002 (0x2712). 10000 is the address of the same function on the meter-side MCU. Reset energy at 10001 is the same in both. Please confirm on a device; the CHANGELOG records the item.

6. Examples

6.1 mbpoll

-0 makes the address zero-based (otherwise mbpoll counts from 1 and you would need -r 1045), -B selects the big-endian word order. Compare with the same value in the HTTP /data response to check the setup.

6.2 Raw Python

The tool tools/lan/modbus_poll.py does this with no extra libraries, and also decodes the identification block. The core is:

7. Troubleshooting

Symptom
Likely cause

Connection refused / timeout

Function bit 15 is off (getFunctionMap), the device is not on the same subnet, or all connection slots are in use

Connected, no response

Frame length wrong or several requests sent without waiting; a bad frame is dropped silently

Exception 02

Range outside 978 ~ 1077 (for example reading 1078 or more in one request)

Exception 01

Function code not 03 / 04 / 06

Strange float values

Wrong word order (use ABCD), or the address is off by one (some tools count from 1)

Signal strength shows positive

It is the absolute value, see Section 4.1

Disconnects after about 30 s

Idle timeout; poll more often or reconnect

TLS handshake fails on 502

The device has no TLS slot (it fell back to plaintext) or the client does not accept the device certificate; see the Overview

  • Overview

  • Telemetry Payload: the same values in JSON

  • Business Command Reference: enablemodbustcp, enabletls, getFunctionMap, modbus (RS485 side)

  • Machine-readable map: spec/modbus-tcp-map.json