Modbus TCP Map
🔍 Feature: Device Locating via LED When multiple meters are installed in a dense electrical panel, send
0x5055to a specific device's Slave ID. The target meter's LED will blink rapidly for 15 seconds, allowing field engineers to visually identify the physical device corresponding to that IP/Slave ID.
Modbus TCP is the most common way for PLCs, industrial gateways and EMS to read the meter. The device is a Modbus TCP server (slave) on port 502: you poll it and read the electrical values from fixed registers. It does not push anything by itself.
1. Introduction
Port
502
Unit ID (Slave ID)
The firmware does not check the Unit ID and echoes it back; use 1
Function codes
0x03 read holding registers, 0x04 read input registers (same data), 0x06 write single register (control registers only)
Readable window
Registers 978 ~ 1077 (100 registers), see Section 4
Word order
A 32-bit value uses two registers, high word at the lower address (ABCD, big-endian)
Switch
Function bit 15 (enablemodbustcp, see Business Command Reference); the server runs only when the bit is set
Concurrent connections
Basic / Lite: 2, Basic+: 1, Pro: 2 (the same number as the TLS slots, see Overview)
Frame size
At most 600 bytes per receive
Which map to use (single / split / three phase) is decided by the product model; read the model string from register 984 (for example SDM01_3PN) or from the model command.
Single-phase
SPM01-D2EW, SPM01-D1EW, SPM01-U1EW
Split-phase
SDM02-EW-12, SDM02-EW-20, SDM02-EW-10U
Three-phase
SPM02-D2EW, SPM02-D1EW, SPM02-U1EW, SDM01-EWM-12, SDM01-EWM-20
2. Connecting
2.1 Plain connection
Open a TCP connection to <device IP>:502 and send standard Modbus TCP frames (MBAP header + PDU). Find the IP with mDNS discovery or from the router.
Connection behavior of the firmware:
A connection may stay open and be reused. If it is idle for 30 seconds the device closes it (custom builds may use 12 s). A client that polls more slowly than that must reconnect.
When all slots are in use, a new connection is not accepted until one slot is released.
The device answers one request at a time. If several complete frames are already queued in the receive buffer, only the newest one is answered. Always wait for the response before sending the next request.
A frame whose declared length does not match is dropped without a response; the client sees a timeout.
Recommended minimum interval between two requests: 150 ms. Polling faster than about once per second is normally unnecessary for energy data.
The Gitbook page says the device accepts only one connection and resets the socket after every read, and asks you to reconnect for every request. The meter keeps the connection. Reconnecting for every request still works and is the safest choice for simple clients, so the recommendation stays compatible. See the CHANGELOG entry for this discrepancy.
2.2 Modbus TCP over TLS
On Basic+ and Pro you can enable Modbus TLS (function bit 14 plus bit 15 in enabletls / enablemodbustcp); the TLS server then also listens on 502. TLS slots are shared with MQTTS, HTTPS and WSS; the service priority is MQTTS > HTTPS > WSS > Modbus TLS, and a Modbus service without a slot falls back to plaintext. Details and limits are in the Overview. Many PLCs and gateways cannot do Modbus over TLS; in that case keep the plaintext connection on a trusted network segment.
3. Function codes and exceptions
0x03 / 0x04
Read registers inside the 978 ~ 1077 window. Start address plus quantity must stay inside the window
0x06
Only the two control registers in Section 5 are writable
Any other
Exception 01
Exception responses:
01 Illegal function
Function code other than 03 / 04 / 06 (including 0x10 write multiple registers)
02 Illegal data address
Read range outside 978 ~ 1077, or write address that is not a control register
03 Illegal data value
Control register written with a value other than the magic value
05
Frame shorter than 12 bytes (non-standard use of this code)
4. Register map
The map below is for the default report mode commonmode = 0. When the device is switched to the generic format (commonmode = 1, see the Business Command Reference), the Modbus read map is switched to a different layout and the tables below do not apply. The device also has mda / minvert commands that remap register addresses or swap bytes for custom integrations. They are not covered here. mda also sets commonmode back to 0 and turns Modbus TCP on. The factory layout is the one below.
4.1 Product identification (base address 978)
Identical on all models. Strings are ASCII packed two characters per register, first character in the high byte. Unused characters are 0.
978
0x03D2
MAC address
6
String (12 characters)
45705E597760
984
0x03D8
Product model
5
String (10 characters)
SDM01_3PN
989
0x03DD
MCU firmware version
5
String (10 characters)
003.00.13
994
0x03E2
Wi-Fi signal strength
1
UINT16
68 means -68 dBm
995
0x03E3
System time
2
UINT32, high word first
Unix seconds
997
0x03E5
Wi-Fi firmware version
3
String (6 characters)
5.1.16
Register 994 holds the absolute value of the RSSI (the firmware writes
-rssiinto an unsigned register). The Gitbook page describes it as a negative dBm value; in the data you read a positive number. Register 989 is the MCU firmware, register 997 the Wi-Fi firmware (the two examples on the Gitbook page are swapped).
4.2 Single-phase metering data
1000
0x03E8
Voltage
FLOAT32
0 ~ 1000
V
1002
0x03EA
Current
FLOAT32
0 ~ 1000
A
1004
0x03EC
Active power
FLOAT32
-1000 ~ 1000
kW
1006
0x03EE
Power factor
FLOAT32
-1.0 ~ 1.0
—
1008
0x03F0
Frequency
FLOAT32
0 ~ 1000
Hz
1010
0x03F2
Import active energy
FLOAT32
±1999999999
kWh
1012
0x03F4
Export active energy
FLOAT32
±1999999999
kWh
1014
0x03F6
Total active energy (import + export)
FLOAT32
±1999999999
kWh
4.3 Split-phase metering data
1000
0x03E8
Voltage L1-N
FLOAT32
0 ~ 1000
V
1002
0x03EA
Voltage L2-N
FLOAT32
0 ~ 1000
V
1006
0x03EE
Current L1
FLOAT32
0 ~ 1000
A
1008
0x03F0
Current L2
FLOAT32
0 ~ 1000
A
1012
0x03F4
Active power L1
FLOAT32
-1000 ~ 1000
kW
1014
0x03F6
Active power L2
FLOAT32
-1000 ~ 1000
kW
1018
0x03FA
Reactive power L1
FLOAT32
-1000 ~ 1000
kVAR
1020
0x03FC
Reactive power L2
FLOAT32
-1000 ~ 1000
kVAR
1024
0x0400
Apparent power L1
FLOAT32
-1000 ~ 1000
kVA
1026
0x0402
Apparent power L2
FLOAT32
-1000 ~ 1000
kVA
1030
0x0406
Power factor L1
FLOAT32
-1.0 ~ 1.0
—
1032
0x0408
Power factor L2
FLOAT32
-1.0 ~ 1.0
—
1036
0x040C
Average voltage L-N
FLOAT32
0 ~ 1000
V
1038
0x040E
Average line current
FLOAT32
0 ~ 1000
A
1040
0x0410
Unbalanced line currents
FLOAT32
-300 ~ 300
%
1042
0x0412
Total line currents
FLOAT32
0 ~ 3000
A
1044
0x0414
Total active power
FLOAT32
-3000 ~ 3000
kW
1046
0x0416
Total reactive power
FLOAT32
-3000 ~ 3000
kVAR
1048
0x0418
Total apparent power
FLOAT32
-3000 ~ 3000
kVA
1050
0x041A
Total power factor
FLOAT32
-1.0 ~ 1.0
—
1052
0x041C
Frequency
FLOAT32
0 ~ 1000
Hz
1054
0x041E
Total import active energy
FLOAT32
±1999999999
kWh
1056
0x0420
Total export active energy
FLOAT32
±1999999999
kWh
1058
0x0422
Total import & export active energy
FLOAT32
±1999999999
kWh
1060
0x0424
L1 import active energy
FLOAT32
±1999999999
kWh
1062
0x0426
L1 export active energy
FLOAT32
±1999999999
kWh
1064
0x0428
L1 import & export active energy
FLOAT32
±1999999999
kWh
1066
0x042A
L2 import active energy
FLOAT32
±1999999999
kWh
1068
0x042C
L2 export active energy
FLOAT32
±1999999999
kWh
1070
0x042E
L2 import & export active energy
FLOAT32
±1999999999
kWh
4.4 Three-phase metering data
1000
0x03E8
Voltage A-N
FLOAT32
0 ~ 1000
V
1002
0x03EA
Voltage B-N
FLOAT32
0 ~ 1000
V
1004
0x03EC
Voltage C-N
FLOAT32
0 ~ 1000
V
1006
0x03EE
Current A
FLOAT32
0 ~ 1000
A
1008
0x03F0
Current B
FLOAT32
0 ~ 1000
A
1010
0x03F2
Current C
FLOAT32
0 ~ 1000
A
1012
0x03F4
Active power A
FLOAT32
-1000 ~ 1000
kW
1014
0x03F6
Active power B
FLOAT32
-1000 ~ 1000
kW
1016
0x03F8
Active power C
FLOAT32
-1000 ~ 1000
kW
1018
0x03FA
Reactive power A
FLOAT32
-1000 ~ 1000
kVAR
1020
0x03FC
Reactive power B
FLOAT32
-1000 ~ 1000
kVAR
1022
0x03FE
Reactive power C
FLOAT32
-1000 ~ 1000
kVAR
1024
0x0400
Apparent power A
FLOAT32
-1000 ~ 1000
kVA
1026
0x0402
Apparent power B
FLOAT32
-1000 ~ 1000
kVA
1028
0x0404
Apparent power C
FLOAT32
-1000 ~ 1000
kVA
1030
0x0406
Power factor A
FLOAT32
-1.0 ~ 1.0
—
1032
0x0408
Power factor B
FLOAT32
-1.0 ~ 1.0
—
1034
0x040A
Power factor C
FLOAT32
-1.0 ~ 1.0
—
1036
0x040C
Average voltage L-N
FLOAT32
0 ~ 1000
V
1038
0x040E
Average line current
FLOAT32
0 ~ 1000
A
1040
0x0410
Unbalanced line currents
FLOAT32
-300 ~ 300
%
1042
0x0412
Total line currents
FLOAT32
0 ~ 3000
A
1044
0x0414
Total active power
FLOAT32
-3000 ~ 3000
kW
1046
0x0416
Total reactive power
FLOAT32
-3000 ~ 3000
kVAR
1048
0x0418
Total apparent power
FLOAT32
-3000 ~ 3000
kVA
1050
0x041A
Total power factor
FLOAT32
-1.0 ~ 1.0
—
1052
0x041C
Frequency
FLOAT32
0 ~ 1000
Hz
1054
0x041E
Total import active energy
FLOAT32
±1999999999
kWh
1056
0x0420
Total export active energy
FLOAT32
±1999999999
kWh
1058
0x0422
Total import & export active energy
FLOAT32
±1999999999
kWh
1060
0x0424
Phase A import active energy
FLOAT32
±1999999999
kWh
1062
0x0426
Phase A export active energy
FLOAT32
±1999999999
kWh
1064
0x0428
Phase A import & export active energy
FLOAT32
±1999999999
kWh
1066
0x042A
Phase B import active energy
FLOAT32
±1999999999
kWh
1068
0x042C
Phase B export active energy
FLOAT32
±1999999999
kWh
1070
0x042E
Phase B import & export active energy
FLOAT32
±1999999999
kWh
1072
0x0430
Phase C import active energy
FLOAT32
±1999999999
kWh
1074
0x0432
Phase C export active energy
FLOAT32
±1999999999
kWh
1076
0x0434
Phase C import & export active energy
FLOAT32
±1999999999
kWh
4.5 Reading FLOAT32 values
All measurements are FLOAT32, two registers each, high word first. For example the registers 0x435C 0x0000 are 0x435C0000 = 220.0. In most libraries this is "Big Endian, word order big / ABCD". If the numbers look wrong (for example 1.6e-41 or huge values) your tool is using word-swapped order (CDAB): switch the setting.
Units: power in kW / kVAR / kVA, energy in kWh, voltage V, current A. This is the same unit as the telemetry JSON in Telemetry Payload; the firmware copies the meter chip registers, so values are not rescaled.
Addresses that are not listed in a table (for example 1004 on the split-phase map) are inside the window but have no defined meaning; do not use them.
5. Control registers
Write with function code 0x06. These registers are outside the read window and cannot be read.
10001
0x2711
Reset energy accumulators
0x51AA (20906)
10002
0x2712
Locate: blink the LED
0x5055 (20565)
A wrong value returns exception
03; a wrong address returns02.Locate blinks the LED (about 15 seconds according to the Gitbook page) so you can find the physical meter in a crowded panel; it does the same as the
locationcommand.Reset energy is irreversible. It is the same as the
zerocommand.
The published page lists the locate register at 10000 (
0x2710). Over Modbus TCP the Wi-Fi module does not handle 10000: locate is at 10002 (0x2712). 10000 is the address of the same function on the meter-side MCU. Reset energy at 10001 is the same in both. Please confirm on a device; the CHANGELOG records the item.
6. Examples
6.1 mbpoll
-0 makes the address zero-based (otherwise mbpoll counts from 1 and you would need -r 1045), -B selects the big-endian word order. Compare with the same value in the HTTP /data response to check the setup.
6.2 Raw Python
The tool tools/lan/modbus_poll.py does this with no extra libraries, and also decodes the identification block. The core is:
7. Troubleshooting
Connection refused / timeout
Function bit 15 is off (getFunctionMap), the device is not on the same subnet, or all connection slots are in use
Connected, no response
Frame length wrong or several requests sent without waiting; a bad frame is dropped silently
Exception 02
Range outside 978 ~ 1077 (for example reading 1078 or more in one request)
Exception 01
Function code not 03 / 04 / 06
Strange float values
Wrong word order (use ABCD), or the address is off by one (some tools count from 1)
Signal strength shows positive
It is the absolute value, see Section 4.1
Disconnects after about 30 s
Idle timeout; poll more often or reconnect
TLS handshake fails on 502
The device has no TLS slot (it fell back to plaintext) or the client does not accept the device certificate; see the Overview
8. Related pages
Overview
Telemetry Payload: the same values in JSON
Business Command Reference:
enablemodbustcp,enabletls,getFunctionMap,modbus(RS485 side)Machine-readable map:
spec/modbus-tcp-map.json