BLE Plaintext API

SPM/SDM Meter Plaintext BLE API

Over Bluetooth Low Energy you can talk to the meter's communication module to: provision 2.4 GHz Wi-Fi, read electrical readings and network status, configure MQTT / UDP / Modbus, switch LAN protocols on or off, and trigger locate / restart / OTA.

The protocol is plaintext UTF-8 JSON. This document is written for system integrators, DIY developers and AI coding assistants.

How the docs are split: this page covers only the transport layer of the plaintext channel (UUIDs, unlock, request/response matching, disconnect and reconnect) plus app-development rules. Provisioning commands, device commands, snapshot fields and business error codes are in the Business Command Reference (shared by plaintext and secured), maintained once for both channels.


1. Quick start (5 minutes)

Minimal loop: connect → subscribe to notifications → unlock → provision Wi-Fi → read the IP to confirm.

Item
Value

Advertised name

<model>-<serial>, e.g. SDM01_3PN-10304B0D7760; filter by prefix SDM / SPM

Service

0xA002

Write (commands)

0xC303

Read (snapshot)

0xC304

Notify (responses)

0xC305

Factory BLE password

1234 (max 16 characters)

Wi-Fi

2.4 GHz only

If you do not want to write code yet, connect to a meter once with the Chrome page or the Windows tool in Section 10 to see the flow and the responses.

1.2 Minimal runnable example for Chrome / Edge

It already includes: serialized sending, event matching (including the pas special case), unlock, provisioning, and polling IP. requestDevice must be triggered by a user click.


2. Build your own app with AI

Give the AI the whole of this page together with the prompt below.

After the AI generates code, self-test it with the acceptance checklist (9.3).


3. Overview and scope

3.1 What you can do

  1. Discover and connect to the device

  2. Unlock the current GATT connection

  3. Send the Wi-Fi SSID and password

  4. Read IP / signal strength / electrical readings

  5. Configure MQTT, UDP and Modbus 485, switch LAN protocols, check / run firmware upgrades

3.2 Does this document apply?

Use this document if both are true:

  • The advertised name starts with SDM / SPM;

  • The GATT service A002 is present.

Do not use this document if:

Situation
Note

The service is A003 and packets contain nonce / ct / tag

Encrypted channel, out of scope

You need to control a relay / breaker

This document has no switching commands

The device has no Wi-Fi

There is no provisioning path described here

You only use HTTP / MQTT, not BLE

See the API document of that channel

3.3 Model differences

Models do not support exactly the same commands. When a command is not supported the device returns a failure: some answer unsupported, others unknow cmd (1015). For example, models without WebSocket have no setInterval; models without LAN TLS have no enablehttps. Clients must handle ok / msg and must not assume that every device has every command.

Identify the product by the advertised name and by TP and SN in the read characteristic, not by what is printed on the enclosure.


4. GATT and session

4.1 UUIDs

Case-insensitive.

Role
16-bit
128-bit

Primary service

0xA002

0000A002-0000-1000-8000-00805F9B34FB

Write (client → meter)

0xC303

0000C303-0000-1000-8000-00805F9B34FB

Read (status snapshot)

0xC304

0000C304-0000-1000-8000-00805F9B34FB

Notify (meter → client)

0xC305

0000C305-0000-1000-8000-00805F9B34FB

4.2 Transport rules

  • Encoding is UTF-8 JSON, no BOM. One command = one Write; one response = one Notify.

  • Subscribe to C305 before the first command, otherwise the device looks unresponsive.

  • Commands must be serialized: write one, wait for its response, then write the next. Do not interleave C304 polling with command writes.

  • Only one BLE connection is supported at a time. While connected the device stops advertising, so other clients cannot see it.

  • MTU: the JSON you write must fit in a single Write (the device accepts about 512 bytes at most; longer input returns payload too large). The device sends each response as one notification and does no application-level fragmentation, so a response cannot exceed MTU - 3 bytes. Measured sizes: model about 200 bytes, mqttdata about 200 bytes, and getwifilist (up to 10 networks) can exceed 300 bytes. If the MTU stays at the default 23, these responses will be truncated and show up as JSON parse errors. The device requests an MTU of 517; on Windows (bleak) 527 was negotiated in testing; on Android call requestMtu(517) after connecting; Web Bluetooth negotiates it in the browser.

  • Do not use A003, C313 / C314 / C315, and do not send nonce / ct / tag.

4.3 Unlock

All business JSON on the write characteristic requires unlocking first. Scanning, connecting and subscribing to notifications do not need a password.

  • Success: {"ok":true,"msg":"Password Correct","event":"pass"}

  • Wrong password: Password Error, code 1003

  • Business command sent while locked: Please unlock, code 1002, event is pas

Meaning of continue:true: within the same BLE connection, later commands do not need pas, and you may read GATT C304 repeatedly. Your app should always send continue:true. The session ends on disconnect or device restart and you must unlock again.

pass can also carry newpas (≤16) to change the password at the same time, or auth (≤40) for phone binding. Normal integrations do not need them.

4.4 Requests and responses

Request (write to C303):

Field
Type
Description

cmd

string

Required in every request

pas

string

Required only for cmd=pass

continue

boolean

Used with pass / read, always true

others

—

See each command

Response (notification on C305):

Field
Type
Description

ok

boolean

Whether the request succeeded

msg

string

English text; compare it verbatim

event

string

Usually equals the request's cmd; pas when locked

code

integer

Present only on failure

d

object

Only query commands carry data

Matching rule (copy it as is):

event == "pas" means the gate was not passed: unlock again, do not keep waiting for the original command.

Suggested timeouts: 8–15 s for normal commands, 20 s for wifi, 25 s for checkota / startota.

4.5 Disconnect and reconnect

The GATT connection is persistent: the device does not close it because of inactivity, but moving away, interference or a device restart will drop it.

Which commands make the device drop GATT:

Command
Drops GATT?
Note

restart

Yes

The device restarts after responding

reset

Yes

Clears the configuration and restarts

mqtr

Yes

Saves the MQTT configuration and restarts

mqtt

No

Saves only, no restart

wifi

No

BLE stays connected after provisioning, so you can keep polling C304 for the IP

enablehttp / enablewebsocket / enablemodbustcp / enabletls / functionMap

No

Only saves the configuration and keeps BLE connected; we recommend sending one restart afterwards, see Business reference 3.3

startota

Usually no

If reboot is 1 the device restarts about 1 s after a successful upgrade; with an HTTPS URL and low memory it may save the URL and restart immediately

all other commands

No

Reconnect algorithm (implement as written):


5. Wi-Fi provisioning

A meter usually leaves the factory without router credentials. The phone connects over BLE first, then sends the 2.4 GHz SSID and the router password. Once it succeeds the meter joins the LAN, and HTTP / MQTT / Modbus TCP and so on become usable.

Everything is written to C303; responses come on C305.

5.1 User flow

  1. Turn on Bluetooth and stand close to the meter.

  2. model-serial appears in the list; connect and enter the BLE password (factory 1234).

  3. Optional: have the meter scan nearby Wi-Fi networks and pick an SSID.

  4. Enter the router password (not the BLE password) and tap "Send to meter".

  5. After about ten seconds read the status; success is IP becoming 192.168.x.x.

5.2 Protocol steps

A. Unlock See 4.3.

B–D. Scan, send SSID / password, confirm online, UI copy: the business-layer commands are identical to the secured channel; see Business Command Reference, Section 2.

The whole flow:


6. Command reference

Write to C303 after unlock. event equals cmd by default.

6.1 Session (plaintext channel only)

cmd

Request

Success msg

Common failures

pass

{"cmd":"pass","pas":"1234","continue":true}

Password Correct

1003

blepassword

{"cmd":"blepassword","old":"1234","new":"654321"}

Password yes

Wrong old password 1026; new password too long 1002 (check msg)

read

{"cmd":"read","continue":true}

ready

resetauth

{"cmd":"resetauth"}

Only needed when phone binding is enabled

Change the default password with blepassword after installation.

6.2 Business commands

Wi-Fi, restart / location / zero / reset / deviceName, model / getFunctionMap / mqttdata / udpdata, LAN switches, MQTT, Modbus 485, UDP and OTA are documented once for both channels: Business Command Reference, Section 3. Command index: Section 4.

Plaintext-specific notes: after a successful restart / reset / mqtr the device drops the GATT link; reconnect per 4.5 and pass again. After changing LAN switches, send one restart.

6.3 Command index (plaintext-only part)

pass, blepassword, read, resetauth (business commands: see the shared command index)

Do not use command or field names that appear in no document.


7. Read characteristic C304: IP and electrical readings

The IP and electrical snapshot is obtained with a GATT Read of C304; do not mix it with notifications.

After pass + continue:true you can simply read repeatedly. If unsure, first send {"cmd":"read","continue":true} and read after you receive ready. When locked, a Read returns {"ok":false,"msg":"Please unlock","code":1002,"event":"read"}.

Numeric readings are mostly decimal strings, not JSON numbers; convert them yourself.

7.1 What you read

The JSON fields you read back (IP / RSSI / FW / SN / TP, electrical keys, units, examples) are the same on both channels; see Business Command Reference, Section 5.


8. Error codes

On failure the notification or the read characteristic is JSON: ok=false, an integer code and an English msg. Success packets have no code.

For configuration failures the BLE code = 1000 + sub-code, so some numbers overlap with fixed codes (especially 1002–1005). Rely on msg; use code only as a hint.

8.1 Common error codes

code

msg

Meaning / action

1000

auth error

Phone-binding string mismatch. Check auth or use resetauth

1001

not authenticated

Binding authentication not completed

1002

Please unlock

Locked. Send pass first. The same code can also be Error password length!

1003

Password Error

Wrong BLE password. Factory default is 1234

1004

No cmd

JSON has no cmd. The same code can also be bad value (invalid number)

1005

No data received

Required parameter missing. The same code can also be unsupported (this model lacks the command)

1026

Old Password Error

Wrong old password in blepassword

1050

payload too large

Write too long, shorten the JSON

Business-layer codes (1014–1044 etc., including Wi-Fi / MQTT / UDP) are in Business Command Reference, Section 6; less common codes: Appendix A.

8.2 Cases without a code

Symptom
Action

msg is illegal cmd / unsupported

This model does not have the command

The client gets no response (timeout)

C305 not subscribed, device restarted, too far away, or responses truncated by a small MTU

The notification is not JSON

Log it and ignore it, do not crash


9. Developer checklist

9.1 Hard rules for apps / AI

  1. Use only A002 / C303 / C304 / C305.

  2. Write UTF-8 JSON with Write With Response; subscribe to C305 first after connecting.

  3. Send pass + continue:true first.

  4. Serialize commands; match by event, mind the pas special case.

  5. Provision only with cmd=wifi; afterwards poll IP in C304.

  6. After restart-type commands, reconnect and unlock again per 4.5.

  7. Do not use commands or fields that are not in this document.

9.2 Suggested module split

scan (name filter) → connect (MTU + notify) → unlock → rpc (write JSON, serialized, wait for event) → provisionWifi → scanWifi (wifiscan + poll getwifilist) → readSnapshot (GATT Read + JSON.parse) → reconnect.

9.3 Acceptance checklist

9.4 Platform notes

Platform
Notes

Android

Call requestMtu(517) after connecting; on status 133 disconnect, wait, then reconnect; keep only one GATT connection at a time

iOS

The MAC address is not available; use the advertised name prefix + service UUID; Web Bluetooth is not available, use Core Bluetooth

Windows

Use bleak in Python; the first scan may prompt for Bluetooth permission

Browser

Chrome / Edge only; needs HTTPS or 127.0.0.1; Firefox and Safari are not supported


10. Demo tools

Both tools use exactly the same protocol as this document. We suggest confirming the meter's behavior with a tool before writing your own app. Both tools have a Chinese / English switch; the JSON they exchange is identical to what is described here and is never translated.

Hosting: the official hosted web page and the Windows tool download address follow the publishing channel and will be added here once released. Tool sources are in this repository: tools/ble-plaintext/ (see tools/README.en.md).

10.1 Chrome / Edge web page

  1. Use Chrome or Edge. file:// pages are often blocked from using Bluetooth, so use an HTTPS page, or run py -3 -m http.server 8765 in tools/ble-plaintext and open http://127.0.0.1:8765/web-ble-console.html.

  2. Click "Select device and connect", choose the meter in the system dialog; it unlocks automatically (the password box defaults to 1234).

  3. Enter the SSID and router password, click "Send Wi-Fi", then click "Read IP / readings".

  4. Tabs on the right: Log, Readings, Comm config (Modbus RTU / MQTT / UDP), Commands / abbreviations.

10.2 Windows GUI tool

Requires PyQt6 and bleak. It provides: scan / connect / unlock, a Wi-Fi list (double-click to fill the SSID), a readings table, a communication-config page, a command / abbreviation cheat sheet, and custom JSON. With "reconnect automatically after device restart" ticked, restart-type commands need no manual reconnect.

10.3 Which one to use

Situation
Use

Demonstrating provisioning, Chrome available

Web page

Factory PC with Python

Windows tool

Writing an iOS app

Follow the JSON in this document and use Core Bluetooth

Writing an Android app

Verify the protocol with the web page first, then write the native app


11. Security notes

The BLE password limits "whether you can change the configuration once connected"; it is not over-the-air encryption. The plaintext channel has no link-layer encryption, so anyone near the device can capture the traffic. The Wi-Fi password is also sent in plaintext during provisioning.

Recommendations:

  • After installation, change the default password 1234 with blepassword;

  • Do not treat BLE as a remote secure channel; send confidential data over HTTPS / MQTTS after the device is online;

  • The plaintext channel does not close GATT automatically when nobody is connected for a long time, so consider physical security for on-site deployments.


Appendix

Appendix A (less common error codes), B (functionMap bits) and C (model short keys) are shared by both channels; see the Business Command Reference.